Stockton Fire Alarm Plan
Submittal Guide
Note from the Stockton Fire
Department: These guidelines have been developed in a cooperative effort by the
Fire Protection Equipment Committee, Fire Prevention Officers Section of the
California Fire Chiefs Association and the State Fire Marshal's Fire Alarm
Advisory Committee. They were established under various editions of the Uniform
Fire Code, the California Fire Code, and National Fire Protection Standard 72.
Related information pertaining to fire alarm requirements for diesel driven
fire pumps can be found at our
Fire Pumps
page.
PLANS AND
FEES (2008/09 Fees Effective July 20, 2008)
Please submit plans and
fees for new fire alarm systems to the Fire Prevention Division, 345 North El
Dorado Street, Stockton, CA 95202. Four sets of plans should be
provided.
LISTED EQUIPMENT
APPLICATIONS
Information should be
provided which clearly identifies the purpose for which the equipment or
devices are listed. This information may be provided by State Fire Marshal
listing sheets and supplemented by manufacturers specification
sheet.
INSTALLATION CODES AND
STANDARDS INCLUDING EDITION
This item refers to the
codes and standards applicable to the specific installation and design
requirements. These typically will include references to specific sections of
Title 24, 2001 Edition, Part 2, California Building Code, Part 3, California
Electrical Code, Part 4, California Mechanical Code and Part 9, California Fire
Code, 2001 Edition. References should also be made to legally adopted editions
of applicable nationally recognized standards such as NFPA 72, 1999 Edition and
local ordinances.
TYPE OF NFPA SYSTEM
PROVIDED
NFPA 72 standard defines
fire alarm systems as Local, Auxiliary, Remote Station, Proprietary or Central
Station. Each has unique characteristics and specific design and installation
requirements. The type of system shall be identified to enable the plan checker
to verify that it is appropriate for the installation.
Note: All life safety
evacuation systems are classified as local.
VOICE MESSAGE CONTENT AND
LANGUAGES
When voice message
evacuation systems are required, as for High-rise and Assembly occupancies, the
content of these messages shall be submitted for approval. Voice messages in
languages other than English shall also be identified when acceptable to the
AHJ. Any alert tones preceding or following the voice message shall also be
described along with the number of times the message will repeat.
SEQUENCE OF
OPERATION.
A written description or
matrix chart shall be provided to define the events, which occur when, various
initiating devices are activated. The description should include details
relating to annunciation, evacuation warning, remote signaling and activation
of fire safety control functions, as applicable.
For example, the activation
of a lobby smoke detector might recall elevators, shut down air handling
systems, close fire doors, sound a general evacuation alarm, transmit an alarm
signal to a central station and annunciate the location at the fire alarm
control panel. A smoke detector in another location may cause a different
sequence of events to occur and this must be clearly identified.
COMBINATION
SYSTEMS
Stockton Fire Department
does not permit combinations (burglar and fire for example). See California
Fire Code Section 1006.3.3.4.
IDENTIFICATION OF AIR
HANDLING SYSTEMS EXCEEDING 2000 CFM
This information shall be
provided to determine whether the provisions of Section 609 of the California
Mechanical Code are applicable.
DESCRIPTION OF SPECIAL
SYSTEM FEATURES AND OPERATIONS
Detailed information should
be provided relating to special features such as pre-signal alarm or positive
alarm sequence for evacuation warning delay, cross zoning of detectors, alarm
verification feature for smoke detectors, and activation of special
extinguishing systems.
REQUEST FOR UL CERTIFICATE
NFPA 72 specifies that a
fire alarm system classified as Central Station Service must have a UL
certificate issued as evidence that the installation is fully in compliance
with applicable NFPA standards and that a maintenance contract is in effect.
However, by local ordinance ALL required fire alarm systems must be UL
Certified.
SYMBOL
LEGEND
The symbols used on plans
and drawings to indicate various fire alarm components and devices shall be
clearly identified in a legend, which indicates quantities of devices along
with manufacturer's names and model numbers. The symbols should be distinctive
and clearly understood by the plan reviewer.
Note: NFPA, NEMA and
others have developed recommended sets of standard fire alarm symbols, which
are commonly used.
IDENTIFICATION OF
OFF-PREMISES SIGNALING METHODS & ON-PREMISES CIRCUIT STYLES
Information pertaining to
the number and types of circuits to be used for transmission of signals to a
remote monitoring facility should be provided, along with the type of
transmission used.
Examples:
Two digital communicator
(dial-up) telephone lines.
One digital communicator
telephone line with one-way RF backup.
A dedicated leased
telephone line with two-way multiplex signal communication.
Two-way RF
System
Style designations as
identified in NFPA 72 should also be provided for on-premises initiating,
signaling line and notification appliance circuits.
ATTIC, CEILING AND BUILDING
CROSS-SECTION DETAILS FOR AREAS WITH AUTOMATIC DETECTION.
Cross section diagrams or
elevation drawings are necessary for areas in which heat, smoke or flame
detectors are provided in order to verify that mounting locations and spacing
of detectors as related to the type of ceiling or roof construction and height
are in accordance with NFPA 72 standards.
SPECIFICATIONS AND DETAILS
ON THROUGH-PENETRATION FIRE STOPPING
Details shall be provided
describing locations of all penetrations of fire-rated walls, ceilings or
assemblies and the type of construction.
Provide sizes, description
and number of cables, conduits or raceways penetrating fire-rated
assemblies.
Provide details on the fire
stopping systems used, including the F and T fire-resistive ratings.
SECONDARY POWER
CALCULATIONS
Calculations shall be
provided to verify that standby batteries or other approved secondary power
source is adequate for the specified standby requirements of the system in the
event of loss of primary power, as specified by NFPA standards.
Calculations shall be based
upon the summation of two calculations: One for supervisory non-alarm condition
and one for the alarm load condition.
The alarm load is generally
based upon the assumption that 10% of the alarm inputs and 100% of the alarm
outputs are in alarm condition.
When a combination (fire
and burglary) system is involved, any non-fire alarm devices, such as burglar
alarm motion detectors, which derive their power from the control panel, must
be included in the supervisory and alarm load calculations.
Current requirements for
individual components in both supervisory and alarm conditions shall be
verified with the manufacturers specification sheets.
A summary of standby
(supervisory) and alarm times as specified by NFPA standards, to be included in
the calculations, are listed below. The calculations will determine the minimum
ampere-hour capacity of the standby battery or minimum requirements for an
equivalent secondary source.
SYSTEM TYPE NORMAL STANDBY
OPERATION ALARM OPERATION
Local 24 Hours 5
Minutes
Auxiliary 60 Hours 5
Minutes
Remote Station 60 Hours 5
Minutes
Proprietary 24 Hours 5
Minutes
Central Station 24 Hours 5
Minutes
Emergency Voice Alarm 24
Hours 1 5 Minutes at full load
VOLTAGE DROP
CALCULATIONS
Calculations shall be
provided to verify that voltage drop in alarm notification appliance circuits
is not excessive. These calculations shall be based upon the length and size
(wire gauge) of the circuit conductors and the maximum alarm current
required.
Generally, when the same
size conductors are used for multiple notification appliance circuits, such
calculation should only be necessary for the longest or worst case
circuit.
The Ohm's law point to
point formula is recommended for these calculations, to determine the voltage
drop in each segment of the circuit based upon the current required, times the
wire resistance.
The summation of the drop
in all segments will then determine the total voltage drop.
As an alternate simpler
method, voltage drop calculations can be based upon the total circuit
resistance times the total circuit load.
The calculated drop in this
instance will always be substantially higher than the actual voltage
drop.
In either case, it is
recommended that the maximum permissible voltage drop not exceed 10% of the
system supply voltage unless local codes specify otherwise.
Voltage (pressure) drop in
a circuit is the result of wire resistance, which is determined by both the
size (diameter) and length. It can be compared with the drop in water pressure
in a hose line resulting from friction loss, with identical factors involved:
the size and length of the hose.
Excessive pressure drop in
a hose line can reduce the flow in GPM to an unacceptable level. Similarly,
excessive voltage drop in a circuit can reduce current flow (amperes) to the
extent that it may be inadequate to properly operate power-consuming electrical
devices.
SINGLE LINE WIRING
DIAGRAM
The single line or 'riser"
diagram indicates system components connected to individual circuits in the
system. Components connected to a common circuit are shown as being connected
by a single line, regardless of the number of conductors actually used for the
circuit. The number of conductors in each wiring segment will be indicated by
right angle marks across the single line at that point or by other appropriate
means.
The term "riser diagram"
frequently used to describe this drawing does not refer to a sprinkler
riser.
CONDUIT FILL
PERCENTAGES
Part 3 of Title 24 CCR, the
California Electrical Code (CEC) limits the amount of conduit fill to a maximum
of 40%. Chapter 9 of Part 3 provides tables indicating the maximum number of
conductors of various sizes, which can be used in various sizes of conduit in
order to comply with the 40% limitations
FIRE ALARM SYSTEM
SUBMITTAL CHECKLIST
This list may help you get
through the process. Please review it before sending in your
plans and documation.
ADMINISTRATIVE
ITEMS
Permit
application.
Payment for plan review and
inspection fees.
Installing contractors
name, address, phone number.
Contractors license &
local business license numbers.
Copy of workers
compensation insurance certificate.
Site address.
Basis for system
installation Building Code occupancy classification.
Building owner and/or
tenant.
FIRE ALARM
EQUIPMENT
Manufacturer's
specification sheets.
Equipment application per
SFM listing and UL/FM approvals.
CSFM building materials SFM
listing numbers.
GENERAL
INFORMATION
Appropriate codes &
standards, including edition.
Type of system or service
involved.
Voice evacuation message
and language(s).
Written sequence of
operation or matrix table.
Combination systems
specific additional uses.
HVAC system
locations greater than 2000 CFM. Please be aware that the California Mechanical
Code is not referring to individual units that are over 2000 CFM. if you have a
room or area served by 3 units each 700 CFM, then you must comply with codes
that require duct detectors.
Special system features
operating instructions.
Required certifications and
placarding.
PLANS &
DRAWINGS
Scaled floor plan,
including north reference.
Completed tide block with
site address.
Include contractor's
business address, telephone, and fax.
Identification of each
room's use.
Location of all components,
including end-of-line devices, if applicable.
Symbol legend, including
quantities, rnanufacturer's name, model.
Identification of circuit
styles, designations and methods.
Description of zone
assignments & device addresses.
Complete budding cross
section, include attic, soffit, or ceiling.
Location of sprinkler
system test valve.
Specifications and details
of through-penetration fire stopping. UL Fire Resistance Directories
Device mounting heights for
manual boxes.
Device mounting heights for
audible devices.
Device mounting heights for
visible notification appliances.
Primary power supply
details.
Secondary power supply
calculations.
Voltage drop
calculations.
SINGLE LINE RISER
DIAGRAM
Conductor information,
including size, stranding, insulation.
Conduit fill calculations
or NEC reference.
Location of end-of-line
devices.